CONSTRUCTION | |||||||||||||||||||||||||||||
Conductor: | - Stranded bare copper Class B per ASTM B-3 | ||||||||||||||||||||||||||||
Insulation: | - Flame-retardant cross-linked polyethylene meeting the requirements for XHHW-2 per UL 44 and the requirements of ICEA S-66-524 for XLPE insulation as standard | ||||||||||||||||||||||||||||
Assembly: | - Conductors shall be cabled in concentric layers with interstices filled with suitable fillers where necessary - A binder tape (when required) of synthetic material assembles the core in a tight circular configuration |
||||||||||||||||||||||||||||
Color Code Chart 107 (E-2): |
|
||||||||||||||||||||||||||||
Jacket: | - Black sunlight resistant, flame retardant polyvinyl chloride per UL 1277 requirements for Type TC power and control cables |
Applications:
- Used as power and control cables in dry and wet locations
- Can be installed in cable trays, raceways, and open air
- Suitable for exposure to weather, direct burial, and for class 1 Division 2 hazardous locations as per NEC
Standards:
- Can be installed in cable trays, raceways, and open air
- Suitable for exposure to weather, direct burial, and for class 1 Division 2 hazardous locations as per NEC
- UL Type TC, 600 Volt
- UL Type XHHW-2, VW-1 Conductors
- ICEA T-29-520 (210,000 BTU/hr)
- IEEE 1202 (70,000 BTU/hr) / CSA FT4
- IEEE 383 (70,000 BTU)
- UL Subject 1277 (70,000 BTU/hr)
- OSHA Acceptable
- Meets cold bend test of -25*C per UL 1277
- Type TC-ER on constructions greater than 2 conductors
- UL Type XHHW-2, VW-1 Conductors
- ICEA T-29-520 (210,000 BTU/hr)
- IEEE 1202 (70,000 BTU/hr) / CSA FT4
- IEEE 383 (70,000 BTU)
- UL Subject 1277 (70,000 BTU/hr)
- OSHA Acceptable
- Meets cold bend test of -25*C per UL 1277
- Type TC-ER on constructions greater than 2 conductors
Part # | AWG Size | No. of Cond. | Nom. Jacket Thick. | Nom. O.D. | Lbs./M’ | Recommended Fitting |
1A51002* | 10 | 2 Flat | .045” | .290” x .480” | 114 | - |
1A51002R* | 10 | 2 | .045” | .455” | 130 | TCF07554A |
1A51003 | 10 | 3 | .045” | .485” | 173 | TCF07554A |
1A51004 | 10 | 4 | .060” | .560” | 236 | TCF07567A |
1A51005 | 10 | 5 | .060” | .615” | 287 | TCF07567A |
1A51007 | 10 | 7 | .060” | .670” | 371 | TCF07578A |
1A51009 | 10 | 9 | .060” | .785” | 479 | TCF10088A |
1A51012 | 10 | 12 | .080” | .920” | 644 | TCF100100A |
1A51014 | 10 | 14 | .080” | 1.05” | 809 | TCF100109A |
*ER Rating only applies to 3 conductors or more